NJR5-ZX keeps the power electronics online after the motor reaches speed.
The 2026 source identifies NJR5-ZX as an online soft starter for squirrel-cage three-phase induction motors, with main-circuit versions for 220, 380, 460, 575 and 690 V and model-current coverage from 15 A to 1000 A.
Voltage suffixes
The final suffix identifies the main-circuit voltage family.
| Suffix | Main-circuit voltage | Published voltage range |
|---|---|---|
| ZX2 | AC 220 V | 198–264 V |
| ZX3 | AC 380 V | 323–437 V |
| ZX4 | AC 460 V | 414–504 V |
| ZX5 | AC 575 V | 517–633 V |
| ZX6 | AC 690 V | 621–759 V |
Representative 380 V selection points
Use motor nameplate current as the primary check; kW is a reference only.
| Model | Rated current | Published 380 V motor power |
|---|---|---|
| NJR5-90/ZX3 | 84 A | 45 kW |
| NJR5-110/ZX3 | 103 A | 55 kW |
| NJR5-150/ZX3 | 140 A | 75 kW |
| NJR5-180/ZX3 | 167 A | 90 kW |
| NJR5-220/ZX3 | 207 A | 110 kW |
| NJR5-320/ZX3 | 300 A | 160 kW |
| NJR5-500/ZX3 | 459 A | 250 kW |
| NJR5-1000/ZX3 | 900 A | 500 kW |
Starting and protection features
The detailed manual lists multiple starting modes and motor-protection functions.
- Six published starting-mode families including current, voltage and torque-based modes
- Soft-start time 2–60 s and soft-stop time 2–60 s
- Current limit adjustable from 50–500% of motor rated current
- Input/output phase loss, imbalance, overload, over/undervoltage and start-time protections
- Built-in RS485 communication using Modbus protocol
- No external bypass contactor required for the online architecture
Thermal-duty checks
Online operation means enclosure ventilation and start frequency matter.
Source reference
Internal database reference for engineering review.
2026 B11 compilation: NJR5-ZX detailed pages 2449–2455, including voltage/current/power tables on pages 2451–2453. B12 overview: page 44.